The picture below shows a Stratos-HSSD 2 with a Stratos-Micra 25 and a Stratos-Micra
100 for size comparison.
ClassiFire-3D
is the most comprehensive intelligence found in a smoke detection system
to date. Not only does it determine the maximum reliable sensitivity
for the environment, but it also controls the dust separator monitoring
for maximum efficiency.
The detection principle used in Stratos-Micra is known as 'forward light
scattering' where the laser beam is diffracted by a small angle by smoke
particles. This principle not only offers high sensitivity, but sensitivity
to a wide range of particle sizes.
A patented feature of the system is that compensation is made for any
contamination in electronic circuitry or hardware, ensuring a long and
trouble free life.
The Stratos range of detectors are the only high sensitivity systems
which are routinely applied to the protection of very dirty and dusty
environments. This is achieved by using Laser Dust Discrimination (LDD)
with a patented dust management and separator system. These features
have greatly extended separator life service intervals. At the other
extreme, Stratos-Micra 25 is capable of providing the very highest levels
of sensitivity in environments such as computer and clean rooms. In
these applications it is able to sense the very smallest amounts of
smoke.
Use of the latest semiconductor laser, electronic components and manufacturing
techniques enable the Stratos-Micra 25 system to be supplied and installed
with a significantly lower whole-life cost then alternative high sensitivity
systems.
Design Limitations
Stratos-Micra 25 is
intended to provide LOCALISED incipient fire detection only. This means
that it is suitable for the substantial range of applications typified
by; small non-compartmentalised rooms, warehouse racking, or pieces
of electronic or electromechanical equipment where it is desirable to
achieve individual incipient fire reporting. In compartmentalised rooms,
each compartment would normally use individual Stratos-Micra 25 detectors.
This product employs
a very low-power aspirator and the aspirating capability of the Stratos-Micra 25
detector is limited accordingly. Stratos-Micra 25 is NOT intended to protect
large areas, or to sample from areas where there may be any difference
in airflow rates or pressure differentials. Application of Stratos-Micra 25
in these circumstances is not recommended. If detection in environments
conforming to these descriptions is required, alternative versions of
Stratos products should be used.
We recommed a maximum
sampling pipe length of 25 metres to be used on the Stratos-Micra 25.
Maximum single length of sampling pipe to be used on the Stratos-Micra
100 detector is 100 metres (or 2 x 50 meter lengths) in still air with
25 sampling holes (or Capillary Remote Sampling Points). This will provide
a transport time from the end of the sampling pipe within 120 seconds.
If the protected area has airflow present, the maximum permitted sampling
pipe length will be reduced.
Stratos-Micra 100
has two pipe inlets and supports a maximum of 100 metres of sampling
pipe.
Stratos-Micra is
available with an optional Piped Exhaust type Docking Station.
This is primarily intended to allow the Stratos-Micra detector to sample
from areas which may be at different air pressure to the detector location.
Typical uses are for air-duct sampling and allowing the installation
of the detector in under-floor or ceiling voids or when sampling from
pieces of computer related equipment.
Stratos-Micra provides
four alarm level outputs and a fault output to the fire alarm panel. Relays
for Fire 1 and Fault are fitted as standard. When an addressable panel
is used the Addressable Protocol Interface Card (APIC)
is used to communicate using the addressable protocol. Using the APIC
means that the alarm and fault relays can be used for other purposes.
Stratos-Micra is supplied with comprehensive
diagnostic facilities as standard. By simply plugging a PC into the serial
port display diagnostic menus will give the capability of fault finding
down to individual component level. ClassiFire-3D
may be viewed working in real time. It is also possible to view a detailed
chart recorder of historical smoke levels showing date, time and alarm
thresholds.
View the Stratos-Micra
25 brochure, Stratos-Micra 100 brochure,
Stratos-Micra 25 Installers Handbook
or the Stratos-Micra 100 Installers
Handbook for more information.
Specification Stratos-Micra 25
| Supply voltage: |
21.6 - 26.4 Volts DC. |
| Current consumption: |
250mA at 24 Volts DC. |
| Size: |
135W x 175H x 80D. |
| Weight: |
1.01 kg. |
| Operating temperature range: |
-10 to +60 deg. Centigrade. |
| Operating humidity range: |
0-90% R.H. non condensing. |
| Sensitivity range(Obsc/m): |
Min = 25% Max = 0.03%. |
| Particle sensitivity range: |
0.003 to 10 microns. |
| Sampling pipe length: |
50 metres max. 25 metres recommended |
| Cabinet rating: |
IP50. |
Specification Stratos-Micra 100
| Supply voltage: |
21.6 - 26.4 Volts DC. |
| Current consumption: |
400mA at 24 Volts DC. |
| Size: |
300W x 180H x 85D. |
| Weight: |
3.7 kg. |
| Operating temperature range: |
-10 to +60 deg. Centigrade. |
| Operating humidity range: |
0-96% non condensing. |
| Sensitivity range(Obsc/m): |
Min = 25% Max = 0.03%. |
| Particle sensitivity range: |
0.003 to 10 microns. |
| Sampling pipe length: |
100 metres |
| Cabinet rating: |
IP50. |