The mimic panel provides a display of all of the status LED's on the Stratos-HSSD® or Stratos-Quadra® detector. The mimic is connected on to the slave loop via a four core screened cable and receives it's power from the Master. All status and alarm LED's on the Master are duplicated on the mimic and the panel is identical in appearance to the front panel of the Stratos detectors.

RESET, TEST and ISOLATE buttons which duplicate those on the Master are provided which may be enabled or disabled individually.
The mimic is designed to fit into a 19 inch rack and is 1.5U high. The illustration shows the optional wall mounting box.
The optional mimic relay board for the Stratos range of detectors adds switching capability for the mimic to drive such devices as beacons or sounders. The relay board fits inside the standard mimic wall mounting box.
| Four relays are provided,
one for each alarm level and one for fault. The fault relay is normally energised so that the board signals fault on power failures. The relays provide common alarms and fault for all detectors attached on the slave loop. The relay board plugs into the mimic via the 6 way connector and is powered from the mimic. |
|
The board requires software revision 3.1 or later to use it's facilities (see technical bulletin 0010 for details of Stratos 3.1 software).